Electrical Permit · ELECTRICAL WIRING OF BF1 NEW SCOPE AS FOLLOWS:
SCOPE OF WORK:
- Provide and install (1) 600A MCB 480/277Y 3PH 4W panel CHFDP in the Cortex area
- Run conduit and with from panel 1DHA2 to provide (1) 600A 480V aluminum feed for panel CHFDP
- Provide and install (1) 600A MCB240/120V 1PH 3W panel AHET in the Cortex area
- Install (1) 150kVA 480V to 208/120Y transformer (Transformer supplied by Base Power)
- Run conduit and wire from panel CHFDP to provide (1) 400A 480V 1PH feed to the transformer
- Run conduit and wire from the transformer to provide (1) 600A 240/120V 1PH 3W feed to panel AHET
- Install (6) 110A 240V 1PH 3W feeds for XE9780L Air-cooled Server and HITL. Fed from panel AHET
- Install (10) 20A 120V outlets for Control + Bench
- Install (4) 40A 480V 3PH twist-lock outlets for forklift chargers fed from panel CHFDP
Electrical Permit · ELECTRICAL WIRING OF BF1 NEW SCOPE AS FOLLOWS:
SCOPE OF WORK:
- Provide and install (1) 600A MCB 480/277Y 3PH 4W panel CHFDP in the Cortex area
- Run conduit and with from panel 1DHA2 to provide (1) 600A 480V aluminum feed for panel CHFDP
- Provide and install (1) 600A MCB240/120V 1PH 3W panel AHET in the Cortex area
- Install (1) 150kVA 480V to 208/120Y transformer (Transformer supplied by Base Power)
- Run conduit and wire from panel CHFDP to provide (1) 400A 480V 1PH feed to the transformer
- Run conduit and wire from the transformer to provide (1) 600A 240/120V 1PH 3W feed to panel AHET
- Install (6) 110A 240V 1PH 3W feeds for XE9780L Air-cooled Server and HITL. Fed from panel AHET
- Install (10) 20A 120V outlets for Control + Bench
- Install (4) 40A 480V 3PH twist-lock outlets for forklift chargers fed from panel CHFDP
No product keyword matched · Austin issued construction permits
Electrical Permit · We will be adding mulitple panels and receptacles for tenant to put in equipment and office area. There will be no additional meter needed.
40 20A 120V. DUPLEX RECEPTACLE
7 - 20A 120V. QUADRAPLEX RECEPTACLE
These 120V outlets being installed are standard NEMA 5-20 (20A 125V duplex outlets). Each will have an FLA of 10A and will be wired with #12 CU stranded wire.
There are also:
(5) 125A 480V equipment feeds with a safety disconnect and #1 CU wire
(3) 70A 480V equipment feeds with a safety disconnect and #4 CU wire
(3) 30A 208V equipment feeds with a safety disconnect and #10 CU wire
No product keyword matched · Austin issued construction permits